Configuration Switches
On a DeviceNet network, each node must be assigned its own unique Mac ID. The Mac ID is
a value between 0 and 63 used to identify each node. The Mac ID and Baud Rate are set us-
ing the DIP switches on the front of the module.
These switches must be set before power is on and cannot be changed during opera-
tion.
Baud Rate Settings
Baud
R
ate
SW
-
1
SW
-
2
125K
OFF
OFF
250K
OFF
ON
500K
ON
OFF
Reserved
ON
ON
Mac ID Settings
M
ac
ID
SW
-
3
(
M
SB)
SW
-
4
SW
-
5
SW
-
6
SW
-
7
SW
-
8
(LSB)
Address 0
OFF
OFF
OFF
OFF
OFF
OFF
Address 1
OFF
OFF
OFF
OFF
OFF
ON
Address 2
OFF
OFF
OFF
OFF
ON
OFF
Address 3
OFF
OFF
OFF
OFF
ON
ON
Addres
s
61
ON
ON
ON
ON
OFF
ON
Address 62
ON
ON
ON
ON
ON
OFF
Address 63
ON
ON
ON
ON
ON
ON
Status LEDs
LED State Description
1 - Reserved - Reserved for future use.
2 - Network Status
Off Not Powered / Not Online
Green solid Link OK, Online, Connected
Green flashing Online, Not connected
Red solid Critical Link Failure
Red flashing Connection Timeout
3 - Module Status
Off
No power to device
Green solid Device operational
Green flashing Data size bigger than configured
Red solid Unrecoverable fault
Red flashing Minor fault
4 - Reserved - Reserved for future use.