User guide
PAGE 4-19
enFORCE Operation Manual
4.8 SW1 - Axis Unit Number Setting
In a multiple SAN Unit system, it is necessary to address each unit for communication purposes.
The number is set with the front DIP switch (4 thru 8) of the SAN Unit. If the display unit is installed,
it must be removed to access the DIP switches.
No two units can share the same number. However, units may be skipped or started from a number
besides one. Typically, units should be numbered sequentially (Ex: 1-31).
DIP Switch Number
Unit
Number
4 5 6 7 8
1 OFF OFF OFF OFF ON
2 OFF OFF OFF ON OFF
3 OFF OFF OFF ON ON
4 OFF OFF ON OFF OFF
5 OFF OFF ON OFF ON
6 OFF OFF ON ON OFF
7 OFF OFF ON ON ON
8 OFF ON OFF OFF OFF
9 OFF ON OFF OFF ON
10 OFF ON OFF ON OFF
11 OFF ON OFF ON ON
12 OFF ON ON OFF OFF
13 OFF ON ON OFF ON
14 OFF ON ON ON OFF
15 OFF ON ON ON ON
16 ON OFF OFF OFF OFF
17 ON OFF OFF OFF ON
18 ON OFF OFF ON OFF
19 ON OFF OFF ON ON
20 ON OFF ON OFF OFF
21 ON OFF ON OFF ON
22 ON OFF ON ON OFF
23 ON OFF ON ON ON
24 ON ON OFF OFF OFF
25 ON ON OFF OFF ON
26 ON ON OFF ON OFF
27 ON ON OFF ON ON
28 ON ON ON OFF OFF
29 ON ON ON OFF ON
30 ON ON ON ON OFF
31 ON ON ON ON ON
Special Settings (positions 1 - 3)
1 ON: CAL/Zero acceptance window = +/-10% of full scale load.
OFF: CAL/Zero acceptance window = +/-4% of full scale load. (Default)
2 ON: Parameter changes made by communicating are not saved on EEPROM.
OFF: Parameter changes made by communicating are saved on EEPROM. (Default)
3 ON: Ramp Down Disabled
The slow down is done rapidly.
It is used to gain cycle time, etc., however, the burden on the gear will be greater.
OFF: Ramp Down Enabled (Default)
The slow down is done slowly.
If not used, set DIP switches number 1 thru 3 in the OFF position.
SAN Unit must be powered off and on again for switch changes to take effect.
RUN
BYPASS
SW1
CON1
POWER
BUSY
SV.
ABN.
ACC.
REJ.
‚`‚e‚b ‚P‚T‚O ‚O
1
2
34
5
6
7
8
OFF‘¤
ON‘¤
DSP1500
Chapter 4: System Setup and Wiring