Owner's manual

enFORCE Operation Manual
PAGE 4 - 6
Chapter 4: System Setup and Wiring
M OT O R
A C 2 00 - 2 2 0 V
P L C
T / D
SAN3-24S
1 :
F
G
2 :
W
3 :
V
4 : U
4.4 Input Power Supply Connection
Adequate circuit protection must be provided for the SAN unit input power.
Recommended conductor size should be a minimum of #16AWG.
Suggested color code (FEC standard): U – Red, V – White, W – Black, FG – Green.
Wiring Chart
SAN3-24S, 40S
3-Phase
3:
180 ~ 242VAC
50/60Hz.
1:FG
SAN3-120S
(Shown Below)
B5:U 3-Phase
A4:V B4:V
180 ~ 242VAC
A3:W B3:W
50/60Hz.
A2:NC B2:NC
A1:FG B1:FG
*Connect wires to both the A side and B side.
Mating Connectors
SAN3-24S, 40S
Manufacture: AMP
Housing Part No.: 1-178128-4
Contact Part No.: 1-175218-3 (Qty.-4)
SAN3-120S
Manufacture: AMP
Housing Part No.: 1-917659-5
Contact Part No.: 1-917511-3 (Qty.-8)
Install adiquate circuit protection on the input
power feed. (Refer to Appendix A for wiring)
When using a transformer that is not isolated or if
incoming power is known to be noisy, install a filter
in the input power circuit. Recommended Filters:
SAN3-24S TDK #ZRWT2205-ME
SAN3-40S TDK #ZRWT2210-ME
SAN3-120S TDK #ZRWT2220-ME