User guide

enFORCE DSP1500 Main Unit Hardware Manual
(Rev. 4.0) PAGE 5 - 62
Chapter 5: Control Interfaces
5.10.1 Component Descriptions
Fieldbus Interface Connection
Pin No. Color Description
1 Blue COM Line
2 Clear Ground
3 Shield COM Line
Termination
Termination of the RIO network requires a terminating resistor at each end of
the network. A termination switch is provided on the front of the interface board.
Set the switch to ON”, if termination is required. If external terminators are
used, the switch must be in the off position.
Configuration Switches
On an A-B Remote I/O network, each node must be assigned its own unique Rack Address. The
Rack Address is a value between 0 and 59 used to identify each node. The Rack Address and
Baud Rate are set using the DIP switches on the front of the module.
These switches must be set before power is on and cannot be changed during operation.
Baud Rate Settings
Baud Rate S
W
-1 SW-2
57.6K OFF OFF
115K ON OFF
230K OFF ON
Reserved ON ON
Rack Address Settings
Rack
Address
SW-3 (MSB) SW-4 SW-5 SW-6 SW-7 SW-8 (LSB)
A
ddress 0 OFF OFF OFF OFF OFF OFF
A
ddress 1 ON OFF OFF OFF OFF OFF
A
ddress 2 OFF ON OFF OFF OFF OFF
A
ddress 3 ON ON OFF OFF OFF OFF
A
ddress 57 ON OFF OFF ON ON ON
A
ddress 58 OFF ON OFF ON ON ON
A
ddress 59 ON ON OFF ON ON ON
Status LEDs
LED State Description
Error OFF Normal Operation
ON - Red Bus off / Error
Active OFF No Communication
ON - Green Communication Active
Power OFF Power Off
ON - Green Power On
O
N
8
5
4
2
3
7
6
1