Install Instructions
Typical Installation
Figure 1
Figure 2
IS-F-860RPZ
INSTALLATION INSTRUCTIONS
MasterSeries
®
 860 and LF860
Reduced Pressure Zone Assemblies
Sizes: 
1
⁄2" – 2" (15 - 50mm)
860
Installation Instructions
1.   Consult local codes for specific installation requirements and restrictions 
applicable to your area.  It is recommended that system supply pressure 
be at least 20 psi (138 kPa).
2.   These instructions apply to models 860, LF860, 860U, and LF860U 
sizes 
1
⁄2" - 2" (15 - 50mm) only. The valves may be installed only in the 
orientation/flow direction as shown. 
3.   THE VALVE ASSEMBLY MUST BE INSTALLED WHERE RELIEF VALVE 
DISCHARGE WILL BE ACCEPTABLE, OR WHERE RELIEF DISCHARGE 
CAND BE COMPLETELY DRAINED. The valve assembly must be 
installed where it is accessible for periodic testing and maintenance. 
Clearances shown in the installation views apply to exterior, interior and 
pit/vault installations and are only recommendations. These minimums 
do not apply to removable protective enclosures. Refer to local codes 
for actual requirements in your area.
   Note: The gap drain is not designed to catch the maximum discharge 
possible from the relief valve.  The installation of FEBCO air gap with 
the drain line terminating above a floor drain will handle any normal 
discharge or nuisance spitting through the relief valve.  However, floor 
drain size may need to be designed to prevent water damage caused by 
a catastrophic failure condition.  Do not reduce the size of the drain line 
from the air gap fitting.
4.   PRIOR TO INSTALLING THE VALVE INTO THE LINE, FLUSH THE 
SUPPLY LINE OF ALL FOREIGN MATERIAL. Failure to flush the supply 
line may cause the check valves to become fouled and require disas-
sembly and cleaning.
5.   After installation SLOWLY fill the assembly with water and bleed air 
from the body using the #2,  # 3 and # 4 test cocks. Test the valve 
assembly to ensure correct operation.
 NOTE: All assemblies are tested at the factory for proper operation and 
leakage. If the valve does not pass the field test, it is most likely due 
to a fouled check valve. This is not covered by the factory warranty. 
The valve cover must be removed and the check seats inspected and 
cleaned. Any damage or improper operation caused by pipeline debris or 
improper installation/start-up is not included inthe factory warranty.
   In case of a possible warranty claim, contact your local supplier or 
FEBCO Representative. DO NOT REMOVE THE VALVE ASSEMBLY 
FROM THE PIPELINE.
6.   The assembly must be protected from freezing and excessive pressure 
increases. Thermal expansion or water hammer can cause pressure 
increases. These excessive pressure situations must be eliminated to 
protect the valve and system from possible damage. 
7.   Plastic testcock plugs and tethers are provided (loose in box) for areas 
that require them.
12" Min (300mm)
Flow
12" Min (300mm)
3" Min (75mm)
18" Min (450mm)
HORIZONTAL INSTALLATION OF THE SERIES 860, LF860 
(Top view, shown with strainer)


