User's Manual

WEMS Installer’s Guide 10
WEMS Software
2) Remove the reset button access screw (Phillips head) on the bottom of
the unit, and using a non-metallic probe, press and hold the reset
button momentarily to bring the unit out of the sleep mode. Replace
the screw.
3) Install the antenna onto the SMA connector on the monitor.
4) On the iEFM and iWPM-T, install the temperature sensor on the
monitor.
5) Using the WEMS Software module PocketConfig, enter the monitor’s
unique serial number and press the Configure button to enter the
unit-level configuration. Refer to Chapter 3, “WEMS Software”, for
more information on using PocketConfig.
6) In the resulting Config tab screen, enter the following information:
a) Enter a value of -3 for the parameter Xmit Power if the antenna
supplied with the unit is the Nearson S467AH-915S Omni whip
antenna. Enter a value of -6 for Xmit Power if the antenna is
the Bluewaby EDY-9432 Yagi antenna. FCC compliance requires
these power settings.
b) Enable the function Sync to PC by ‘checking’ (D) this
parameter.
Once the proper value for Xmit Power is entered and Sync to PC is enabled,
select the Set Parameters button and wait for the progress screen to
complete.
7) Verify that the settings were accepted by checking the Current Device
Settings window.
iCCU Installation Instructions
The following instructions are to be performed for the iCCU at installation.
1) Remove the iCCU packing carton.
2) Remove the enclosure cover. Locate the unattached red wire and
attach it to the positive terminal on the battery. Replace the cover.
3) Using the WEMS Software module PocketConfig, enter the iCCU’s
unique serial number and press the Configure button to enter the
unit-level configuration. Refer to Chapter 3, “WEMS Software”, for
more information on using PocketConfig.