Brochure
2.000
2.312
1.625
1.625
2.060
2.635
73
CONTACTORS
Poles
1
2
F/L
Inductive
Amps
30
40
30
40
Locked
Rotor Amps
240/480/600
150/125/100
240/200/160
150/125/100
240/200/160
Resistive
Amps
40
50
40
50
Coil
AC Volts
24
120
208/240
24
120
208/240
24
120
208/240
24
120
208/240
Coil VA
Inrush
60 HZ
28
28
30
30
Coil VA
Sealed
60 HZ
5
5
6.5
6.5
Coil VA
Inrush
50 HZ
31
31
33
33
Coil VA
Sealed
50 HZ
6
6
8
8
HP
120 Vac
1 PH
1
2
2
2
HP
240 Vac
1 PH
2
3
3
3
Model
H130A
H130B
H130C
H140A
H140B
H140C
H230A
H230B
H230C
H240A
H240B
H240C
Figure
1
2
3
4
DEFINITE PURPOSE CONTACTORS (continued on next page)
3 and 4 POLE DEFINITE CONTACTORS AND REVERSING CONTACTORS pages 74-75.
1.625
2.312
1.625
2.000
2.000
2.576
Fig. 1 Single Pole Fig. 2 Single Pole
Fig. 3 Two Pole Fig. 4 Two Pole
• Fasco contactors meet
specifications for devices
up to 600 VAC in accordance
with U.L. Bulletin No. 508,
“Industrial Control
Equipment.”
• U.L. and CSA approved.
• Coils have Class B insulation.
• 30 Amp - Screws and quick
connect terminals
• 40 Amp - Lugs and quick
connect terminals
2.576
2.635
2.060
1.625
1.625
1.625
1.625
2.312
2.312
2
2
2