fantech
Fan Sections & Motors
Fans shall be Ebm-Papst backward inclined motorized impellers.
Fan motor shall have maintenance-free permanently lubricated sealed ball bearings.
Fan motor shall be (TOP) thermal overload protected.
Fan motor shall be UL listed to UL1004 and/or UL2111, CSA C22.2 No. 77 and No.100.
Fan motor shall have IP protection class 44 according to DIN 40 050.
Separate fans for exhaust and supply blowers shall be provided.
Filters
The exhaust and fresh air streams shall both be protected by MERV1 (MERV6 optional) washable filters constructed to meet UL 900.
Part III – Execution
Serviceability
Unit shall have hinged and/or screwed access panels on front and back.
Cores, filters and motors shall be serviceable from either sides of the unit.
Fan assemblies shall be mounted on a removable sliding base. Energy recovery cores and filters shall be mounted in slide-out rails for ease of
inspection, removal, and cleaning.
Accessibility to the electrical box shall be maintained for any unit installation.
Installation
Unit shall be rod mounted or seated on a platform.
Flanged connection shall be provided for suitable ductwork connection.
Unit shall be adaptable for easy service of electrical components.
Warranty
Fantech ERV’s have a warranty that is limited to 3 years on all parts from the date of purchase, including parts replaced during this time
period. If there is no proof of purchase available, the date associated with the serial number will be used for the beginning of the warranty
period.