User Guide

Guide Specification
Fantech Commercial Energy Recovery Ventilator
Ducted Indoor Model
SER11504N
United States · 10048 Industrial Blvd. · Lenexa, KS 66215 Canada · 50 Kanalflakt Way. · Bouctouche, NB E4S 3M5
Phone: 800.747.1762; 913.752.6000 Phone: 800.565.3548; 506.743.9500
Fax: 800.487.9915; 913.752.6466 Fax: 877.747.8116; 506.743.9600
www.fantech.net
; info@fantech.net
Fantech, reserves the right to modify, at any time and without notice, any or all of its products features,
designs, components and specifications to maintain their technological leadership position.
Part I – General
A. Product Specification
Energy recovery ventilator shall be as manufactured by "Fantech" or approved equal provided all specifications are
met. Fantech SER commercial series shall be used as the basis of design.
B. Requirements
1. Unit shall be CSA Certified to safety standards CSA C22.2 No. 113 Fans and Ventilators and UL 1812 Ducted
Heat Recovery Ventilators.
2. Performance shall be as scheduled on plans.
3. Exhaust discharge and outside air intake shall be located on the same side.
4. The unit shall be capable of operating in winter conditions without frost buildup.
5. The heat recovery core shall be of aluminum fixed plate, cross flow construction, with no moving parts.
Part II – Product
A. Cabinet
1. Cabinet shall be constructed of G90 galvanized, 20 gauge steel sheet with lapped corners. All exposed surfaces
shall be coated with baked powder paint. All seams shall be sealed, requiring no caulking at job site.
2. The unit shall be fitted with a full length drain pan for controlled condensate drainage including two drains spouts
with 12.7mm (½ inch) barbed fittings for easy connection.
3. Unit casing shall be insulated with 25mm (1 inch) and 50mm (2 inch) foil-faced high density polystyrene foam for
condensation control. The flame spread index of the insulation material shall not be over 25 and its smoke
developed index shall not be over 50 when tested in accordance with the Standard for Tests for Surface Burning
Characteristics of Building Material, UL723. Insulation shall be secured to unit with waterproof adhesive and
permanent mechanical fasteners.
B. Energy Recovery Core
1. The energy recovery core shall be manufactured from a flame-proof/polyester-based synthetic paper which is
designed to transfer sensible and latent energy. The flame spread index of the energy recovery core shall not be
over 25 and its smoke developed index shall not be over 50 when tested in accordance with the Standard for
Tests for Surface Burning Characteristics of Building Material, UL723.
C. Electrical
1. Electrical box shall be isolated from the airflows and all integral wires and connections protected.
2. All internal electrical components shall be factory wired for single point power connection.
3. All electrical components shall be UL Listed or Recognized and CSA Certified or Accepted where applicable and
wired in compliance with the National Electrical Code.
D. Fan Sections & Motors
1. Fans shall be Ebm-Papst backward inclined motorized impellers.