Product Brochure

6
|
Ventilation Solutions for Radon Mitigation
UV resistant, UL Listed durable plastic
UL Listed for outdoor use
Automatic reset thermal overload protection
Vibration welded seam ensures leak proof housing
Model
Duct
size
Rated
power
Voltage /
phase
Max.
amps
0.5” P
s
1.0” P
s
1.25” P
s
1.5” P
s
1.75” P
s
2.0” P
s
Max P
s
Shipping
weight
Item #
Dimensions
inch W V / ~ A in.wg lbs A B C D E
HP 190 4 / 5 56 120 / 1 0.54 137 94 73 50 23 2 2.01 7 411297 3 31/32 4 31/32 10
1
10 9/16
FR 150 (Radon) 6 66 120 / 1 0.59 222 120 77 34 - - 1.70 8 56014
5 7/8 11 1/2
1 1/4 9 1/4
-
HP 220 6 128 120 / 1 1.20 285 183 155 125 90 57 2.34 8 411349 5 7/8 11 1/2 1 1/4 9 1/4 -
HP 2133 4 1/2 20 120 / 1 0.17 86 - - - - - 0.88 4 45044 4 15/32 10 1 1/4 9 1/4 -
HP 2190 4 1/2 58 120 / 1 0.58 216 102 79 51 26 - 1.98 7 45048 4 15/32 10 1 1/4 9 1/4 -
The performance shown in this brochure is representative of the actual test results recorded at Texas Engineering Experiment Station/Energy Systems Lab, a recognized testing authority for HVI.
Testing was done in accordance with HVI 916 Test Procedures. Dimensions are shown in inches.
Application
HP & FR Series fans are specially designed with higher pressure capabilities
for radon mitigation applications.
How it works
Active radon mitigation systems employ specialized fans to exhaust radon gas
from underneath building structures via a sealed pipe system. Such systems
are designed to remove radon gas before it migrates to a building's interior.
Design
The fans feature a fully sealed plastic housing. The housing is joined via a
vibration welding process. The process uses transverse, reciprocating motion
under pressure at the point of contact between the housing’s inlet and outlet
pieces. The friction produces heat that melts the thermoplastic material at the
interface. The melted material quickly re-solidifies, resulting in a fused, single-
piece housing. The fused seam is inherently air tight, very strong and permanent.
No screws or adhesive is used to join the housing pieces. An air-tight fan ensures
that efficiency is not lost and contaminants are not spilled due to leakage.
The fan can be mounted both indoor, outdoor and in wet locations. These fans
feature external rotor motors that have proven dependable year after year.
A large electrical wiring enclosure is designed into the fan housing, making
electrical installation easier. Thermal overload protected with automatic reset.
Certification
Specification data
Inline Radon Fans
HP and FR Series
HP 2133
For applications where lower pressure and
flow are needed. Low power consumption.