CO2RT-R is a room sensor for measuring carbon dioxide levels in air.
They have a built-in relay with switching output.
When the CO
2
level goes above the set point the unit will go into high
speed.
Dimensions
B
A
C
A B C
100 85 30
Dimensions are in mm.
Ambient Temperature
23...+131°F (-5...+55°C)
Ambient Humidity 0..90% RH, non-condensating
Long Term Stability typ. 20 ppm / year
Response Time < 90 s
Warm-up Time < 5 s
Protection Class IP30
Measuring Principale NDIR (Non-Dispersive Infrared Technology)
Working Range CO
2
0...2000 ppm
Accuracy CO
2
at 38°F
(20°C)
< ± (50 ppm +2% of measuring value)
Technical Data
Switching output
Max. switching voltage 50 V AC / 60 V DC
Max. switching load 1 A at 50 V AC, 1 A at 30 V DC
Min. switching load 1 mA at 5 V DC
Contact material Ag+Au clad
CO2RT-R est un capteur d’ambiance pour mesurer les niveaux de dioxyde
de carbone dans l’air. Ils ont un relais intégré avec sortie de
commutation.
Lorsque le niveau de CO
2
dépasse le point de consigne, l’appareil passe
en haute vitesse.
Lire ces instructions avant le montage et le
raccordement de ce produit
Température ambiante
23...+131°F (-5...+55°C)
Humidité ambiante 0..90% HR, sans condensation
Stabilité à long terme typ. 20 ppm / an
Temps de réponse < 90 s
Temps de préchauffage < 5 s
Classe de protection IP30
Principe de mesure NDIR (Rayonnement Infrarouge Non Disper-
sif)
Plage de mesure CO
2
0...2000 ppm
Précision CO
2
à 38°F
(20°C)
< ±(50 ppm +2% de la valeur mesurée)
Technical Data
Switching output
Max. switching voltage 50 V AC / 60 V DC
Max. switching load 1 A at 50 V AC, 1 A at 30 V DC
Min. switching load 1 mA at 5 V DC