Guide Specification
Item #: 424525
Rev Date: 2015-05-12
FIT
®
120E
Energy Recovery Ventilator
Part I – General
Product Specification
Energy recovery ventilator shall be manufactured by “Fantech” or an approved equal provided all specifications are met. Fantech ERV residential
series shall be used as the basis of design.
Requirements
Unit shall comply with the UL 1812 requirements regulating the construction and installation of Heat Recovery Ventilators.
Complies with the CSA C22.2 no. 113 Standard applicable to ventilators.
Complies with the CSA F326 requirements regulating the installation of Heat Recovery Ventilators.
Technical data was obtained from publishing results of test relating to CSA C439 Standards.
The unit shall be HVI certified.
Part II – Product
Cabinet
Cabinet shall be constructed of G90 galvanized, 24 gauge steel sheet. All seams shall be sealed, requiring no caulking at job site.
Cabinet shall be insulated with 1 in. (25 mm) of foil-faced high density polystyrene foam an 0.25 in. (6 mm) of closed-cell foam on the top of
the unit.
Cabinet shall be of a height of 8.75” (222mm)
Energy Recovery Core
The energy recovery core shall be manufactured from a flame rated polymer membrane which is designed to transfer sensible and latent
energy. The flame spread index of the energy recovery core shall not be over 25 and its smoke developed index shall not be over 50 when
tested in accordance with the Standard for Tests for Surface Burning Characteristics of Building Material, UL723.
Energy recovery core features polymer membrane with ISO 846 certified antimicrobial protection.
The energy recovery core shall be freeze tolerant and water washable.
Energy recovery core shall be AHRI listed for performance.
Frost Prevention
A preset frost prevention sequence is activated at an outdoor air temperature of 14°F (-10°C) and lower. During the frost prevention sequence,
the supply blower shuts down and the exhaust blower switches into high speed to maximize the effectiveness of the frost prevention strategy.
The unit then returns to normal operation, and continues cycle.
Electrical
Electrical box shall be isolated from the airflows and all integral wires and connections protected.
All internal electrical components shall be factory wired for single point power connection.
All electrical components shall be UL Listed or Recognized and CSA Certified or Accepted where applicable and wired in compliance with the
National Electrical Code.
Control
Low-voltage remote controls connections.
Field selectable Reduced or Normal speed continuous operation switch.