Submittal Sheet
Specification Sheet
Item #:422552
Rev Date: 2020-01-16
FIT
®
120E
Energy Recovery Ventilator
Product #: 44940
With a profile of only 8.75" high, Fantech's FIT 120E is ideally suited for
condos and apartments that have no mechanical room and where it must
be located over a false ceiling. The FIT 120E brings a continuous supply
of fresh air into a home while exhausting an equal amount of
contaminated air. The energy recovery core at the center of the unit
transfers heat and moisture from the incoming air to the outgoing air
that was cooled and dried by the building's air conditioner.
Features
• Slim design, only 8.75" (222 mm) high
• No drain required
• Easy to install ceiling bracket included
• Weight: only 36 lbs (16 kg) including core
• Fans with backward curved RadiCAL blade
• Electrostatic filters (washable)
• Easy Core Guide Channels For Removing Core
• Multiple speed operation
Optional Controls
• ECO-Touch™ (#44929) – Programmable Touch Screen Wall Control
• EDF7 (#44883) – Electronic multi-function dehumidistat
• EDF1 (#40375) – Multi-function control
• RTS5 (#44794) – 20/40/60 minute over-ride
• RTS2 (#40164) – 20 minute over-ride
• MDEH1 (#40172) – Dehumidistat
Specifications
• Duct size – 5" (125 mm) oval
• Voltage/Phase – 120/1
• Power rated – 170 W
• Amp – 1.4 A
• Average airflow – 106 cfm (50 L/s)
@ 0.4" P
s
(100Pa)
Fans
Two (2) factory-balanced fans with backward curved blades. Motors come
with permanently lubricated, sealed ball-bearings to guarantee long life
and maintenance-free operation.
Energy Recovery Core
AHRI certified core made from water vapor transport durable polymer
membrane that is highly permeable to humidity. The ERV core is freeze
tolerant and water washable. Core dimensions are 11.5” x 11.5” (290 x
290 mm) with a 7.8” (198 mm) depth.
Frost Prevention
A preset frost prevention sequence is activated at an outdoor air
temperature of 14°F (-10°C) and lower. During the frost prevention
sequence, the supply blower shuts down and the exhaust blower switches
into high speed to maximize the effectiveness of the frost prevention
strategy. The unit then returns to normal operation, and continues cycle.
Serviceability
Core, lters, fans and electrical panel can be accessed easily from
the access panel. Core conveniently slides out with only 8” (203 mm)
clearance.
Cabinet
24 gauge G90 galvanized steel.
Insulation
Insulated with 1 in. (25 mm) of foil-faced high density polystyrene foam
an 0.25 in. (6 mm) of closed-cell foam on the top of the unit.
Filters
Two (2) washable electrostatic panel type air filters. Exhaust air filter
dimensions 11.2” (284mm) x 7” (176 mm) x 0.125” (3mm). Supply air
filter dimensions 11.4” (289mm) x 7.7” (196 mm) x 0.125” (3mm).
Installation
Unit is typically hung by using ceiling bracket supplied with unit. Optional
chain kit available.
Warranty
5 years on energy recovery core, 7 year on motors, and 5 year on parts.