Fire signalisation cable J-Y(St)Y ... Lg
conductor material: bare copper
conductor construction: solid, class 1
insulation: PVC TI1
stranding unit: pair
stranding: layers
screen over strand: foil
drain wire: yes
sheathing material: PVC TM1
colour of outer sheath: red
flame retardant: VDE 0482-332-1-2/IEC 60332-1
max. operating temperature,
fixed:
-30 - +70 °C
temperature, moved/during
installation:
-5 - +50 °C
bending radius, fixed
installation:
7,5 x DA
bending radius, single bend: 2,5 x DA
insulation resistance: 100 MOhmxkm
operating capacity: 100 nF/km
nominal voltage U: 300 V
core identification: colours acc. VDE 0815
Application: For connection of telecommunication units inside of buildings in dry and wet rooms, also outdoors if the
cable is protected against direct sun irradiation. The special imprint identifies the cable as fire signalisation cable.
Additional information: Stranding: cores twisted into pairs (2-pairs cable stranded as star-quad), pairs stranded in
layers. Core identification: two-pair cable: red, black, white, yellow. More than two-pairs are in continuous sequence:
white-blue, white-yellow, white-green, white-brown, white-black. In the 1-st pair of each layer there is one red core in
place of the white one.
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Table: Technical characteristics Fire signalisation cable
p/n part name D
A.
[mm]
G
.
[kg/km]
Cu
.
[kg/km]
100947 Brandmeldekabel 01X2X0,8
RT
5,5 38 11
100056 Brandmeldekabel 02X2X0,8
RT
7 55 21
100057 Brandmeldekabel 04X2X0,8
RT
9 95 41
p/n part name D
A.
[mm]
G
.
[kg/km]
Cu
.
[kg/km]
100948 Brandmeldekabel 05X2X0,8
RT
9,4 114 52
100058 Brandmeldekabel 06X2X0,8
RT
10,5 130 62
100059 Brandmeldekabel 10X2X0,8
RT