Data Sheet

© 2022 · Klaus Faber AG · all rights reserved KLAUS FABER AG · Europaallee 33 · 66113 Saarbrücken · Germany · T +49 681 9711 - 0 dbl_bmk.pdf / Issue 02/17/2022 / page 1/2
Fire signalisation cable
J-Y(St)Y ... Lg (BMK)
Application: For the connection of telecommunication units inside buildings in and under plaster in dry and wet rooms. Also sui-
table for installation outdoors if the cable is protected from sunlight. By the special sheath imprint -Brandmeldekabel- this cable
is particularly designed for the use in re signalisation systems.
Stranding: cores twisted into pairs (2-pairs cable stranded as star-quad), pairs stranded in layers. Core identication: two-pair
cable: red, black, white, yellow. More than two-pairs are in continuous sequence: white-blue, white-yellow, white-green, whi-
te-brown, white-black. In the 1-st pair of each layer there is one red core in place of the white one.
Construction and technical data:
CPR-classication according to EN 50575: Eca
Conductor material: copper, bare
Conductor construction: Class 1 = solid
Insulation: PVC TI1
Stranding unit: pair
Stranding: Layers
Screen over strand: Foil
Drain wire: yes
Sheathing material: PVC YM1
Colour of outer sheath: red
Flame-retardant: VDE 0482-332-1-2/IEC 60332-1-2
Permitted outer cable temperature, xed, °C: -30 - +70 °C
Permitted outer cable temperature, moved, °C: -5 - +50 °C
Bending radius, xed installation: 7.5 x Ø
Bending radius, single bend: 2.5 x Ø
Insulation resistance: 100 MOhmxkm