Data Sheet
dbl_yjz_600.pdfIssue23.11.2018 · Klaus Faber AG · Lebacher Straße 152 – 156 · 66113 Saarbrücken · Germany · Phone +49 681 9711-0 · Fax -289
Control cable YSLY 600
CPR-performance: Eca
Conductor material: copper, bare
Conductor class: class 5 = fine stranded
Insulation: PVC
Sheathing material: special PVC-compound
Colour outer sheath: black
Flame-retardant: VDE 0482-332-1-2/IEC 60332-1-2
Oil-resistant: EN 60811-404
Maximum permitted
conductor temperature:
70 °C
Permitted outer cable
temperature, fixed:
-40 - +70 °C
Permitted outer cable
temperature, in motion/
during installation:
-5 - +70 °C
Bending radius, fixed
installation:
4 x DA
YSLY-JZ 600 YSLY-OZ 600 Y-JB 600
Nominal voltage Uo: 600 V 600 V 600 V
Nominal voltage U: 1 kV 1 kV 1 kV
Test voltage: 4 kV 4 kV 4 kV
Protective conductor: yes no yes
Core identification: green-yellow + numbers numbers colours acc. to VDE 0293
(HD308)
Application: Flexible power, process control and instrumentation cable for industry, machinery and outdoor
environment. The cable is resistant to UV-irradiation, to most commonly used chemicals and to oil and grease. Not
suitable for constant motion.
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Table: Technical characteristics YSLY-JZ 600
p/n part name R
l.
[Ω/km]
R
bv.
[mm]
D
A.
[mm]
Cu
.
[kg/km]
G
.
[kg/km]
033581 YSLY-JZ 600 03X0,75 26 35 8,7 22 91
033582 YSLY-JZ 600 04X0,75 26 37 9,2 29 120
033583 YSLY-JZ 600 05X0,75 26 40 9,9 36 134
033585 YSLY-JZ 600 07X0,75 26 44 11,1 50,4 177
033589 YSLY-JZ 600 12X0,75 26 54 13,4 86,4 248
033592 YSLY-JZ 600 18X0,75 26 62 15,6 130 350
033595 YSLY-JZ 600 25X0,75 26 76 18,9 180 478