Data Sheet
dbl_nhxmh.pdfIssue23.11.2018 · Klaus Faber AG · Lebacher Straße 152 – 156 · 66113 Saarbrücken · Germany · Phone +49 681 9711-0 · Fax -289
LSOH building wire NHXMH-
J/-O acc. to VDE 0250 T. 214
CPR-performance: Eca
Conductor material: copper, bare
Conductor class: class 1, up from 16 sqmm class 2
Insulation: XLPE 2XI1
Sheathing material: FRNC-compound HM2
Flame-retardant: VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
Smoke density: DIN EN 61034/IEC 61034
Halogen-free: DIN EN 50267/IEC 60754
Maximum permitted
conductor temperature:
70 °C
Permitted outer cable
temperature, fixed:
-40 - +70 °C
Permitted outer cable
temperature, in motion/
during installation:
5 - 70 °C
NHXMH-J NHXMH-O
Nominal voltage Uo: 300 V 300 V
Nominal voltage U: 500 V 500 V
Test voltage: 2 kV 2 kV
Protective conductor: yes no
Core identification: colours acc. to VDE 0293 (HD308) colours acc. to VDE 0293 (HD308)
Application: Low-smoke, zero-halogen, flame-retardant building wire, for installation on and under plaster in dry
and wet rooms, as well as in concrete (except for shaken, jolted, tamped concrete). For indoor use only, primarily in
buildings with a high concentration of people and material assets.
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Table: Technical characteristics NHXMH-J
p/n part name
.
R
l.
[Ω/km]
I
bl.
[A]
R
bv.
[mm]
D
A.
[mm]
Cu
.
[kg/km]
G
.
[kg/km]
020278 01X1.5 RE 12,1 20,8 5,2 15 75
020279 01X2.5 RE 7,41 22,4 5,6 24 85
020232 01X4 RE 4,61 28 7 39 135
020280 01X6 RE 3,08 29,6 7,4 58 150
020281 01X10 RE 1,83 31,2 7,8 96 200
020233 01X16 RM 1,15 38,4 9,6 154 295
020282 01X25 RM 0,727 48 12 240 350
020185 03X1.5 RE 12,1 19,5 34,4 8,6 43 130
020188 03X2.5 RE 7,41 27 38 9,5 72 165
020206 03X4 RE 4,61 36 42 10,7 115 235