Data Sheet
© 2022 · Klaus Faber AG · all rights reserved KLAUS FABER AG · Europaallee 33 · 66113 Saarbrücken · Germany · T +49 681 9711 - 0 dbl_nhxmh.pdf / Issue 02/17/2022 / page 1/3
LSOH building wire
NHXMH-J/-O
Application: Low-smoke, zero-halogen, ame-retardant building wire, for installation on and under plaster in dry and wet
rooms, as well as in concrete (except for shaken, jolted, tamped concrete). For indoor use only, primarily in buildings with a high
concentration of people and material assets.
Construction and technical data:
CPR-classication according to EN 50575: Dca
Standard: VDE 0250 T. 214
Conductor material: copper, bare
Conductor construction: class 1, up from 16 sqmm class 2
Insulation: XLPE 2XI1
Sheathing material: FRNC-compound HM2
Flame-retardant: VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
Smoke density: DIN EN 61034/IEC 61034
Halogen-free: DIN EN 50267/IEC 60754
Max. temperature at conductor, °C: 70 °C
Permitted outer cable temperature, xed, °C: -40 - +70 °C
Permitted outer cable temperature, moved, °C: 5 - 70 °C
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the ability of
shipment. Outer diameters are approximately.
NHXMH-J
Nominal voltage Uo: 300 V
Nominal voltage U: 500 V
Test voltage: 2 kV
Protective conductor: yes
Core identication: colours acc. to VDE 0293 (HD308)
part
no.
part name Rl
[Ohm/km]
Ibl
[A]
Rbv
[mm]
Ø
[mm]
Cu G
[kg]
020278 01X1.5 RE 12.1 20.8 5.2 15 75
020279 01X2.5 RE 7.41 22.4 5.6 24 85