Instructions
Wiring Instructions for JL-103B Photocell
The Correct Wiring for JL-103B Photocell
• JL-103B RED Load wire connected with LED xture ‘L’ terminal
• Then LED xture ‘N’ terminal connect with both JL-103B Black Neutral wire and AC input
Blue Neutral wire
• Then JL-103B White Line wire connect with AC input Brown Active wire
• Then LED xture ‘GND’ terminal connect with the AC input Green/Yellow Earth wire
The most common Incorrect Wiring for JL-103B Photocell:
• Red Load wire of JL-103B directly connected to AC input Active wire
• White Line wire of JL-103B connected to the LED xture ‘L’ terminal
www.eyelighting.com.au
1800 635 383
Results of the Incorrect Wiring:
• The Lighting xture will be ON/OFF every couple of seconds
How to Correctly Wire JL-103B Photocell
JL-103B
Photocell
GND
N (Neutral)
L (Active)
Fixture
Load
Neutral
LINE
Incorrect Wiring
L (Active)
N (Neutral)
GND
JL-103B
Photocell
Fixture
Load
Neutral
LINE
Safety Note: This PE Cell must be installed by a licensed electrician, following the installation instructions. Before carrying out
any installation or maintenance on this PE Cell, ensure that the mains supply is fully isolated. Any inadequate installation might
cause falling, electric shock, re, or other hazards. Do not modify the PE Cell. Do not touch the PE Cell when the luminaire is
operating. Installer shall bear the consequences if the PE Cells are not secured in a proper manner. Any modication on the
PE Cells or luminaire to which PE Cell is connected will void the warranty.
JLWIR13323