Allow sufficient spacing for adequate ventilation
Flexible conduit adapter kit installation
W
The circuit breaker used for this connection should
be rated no lower than 20 amps and no greater than
30 amps.
W
This unit must be installed in accordance with the
National Electrical Code and with all local codes.
An ALL-POLE MAINS SWITCH with a contact
separation of at least 3 mm in each pole shall be
incorporated in the electrical installation of the
building. The installation shall be carried out in
accordance with all applicable installation rules.
W
Installation and service must be performed by a
qualified electrician only.
C
A UL listed electrical distribution box is
recommended for the termination of the conduit
opposite the XPA. See the following "UL
requirements" section.
The optional Flexible Conduit Adapter Kit (Extron part
#70-228-02) consists of
• One EMT adapter plate
• One 6-foot long electrical conduit
• Three 7.5 feet, 18-gauge spade connector power wires
• One UL rated zip tie wrap
• Three auxiliary crimp style spade connectors designed for
14- to 16-gauge wires
N
If needed, Extron recommends using a UL-rated crimp
tool to terminate the spade connectors. One recommended
choice is the Molex crimp tool (Molex part #19285-0008).