User`s manual

XTRA Series • Installation
2-5
Use 2 mounting holes on
opposite corners.
(2) 4-40 x 3/16"
Screws
NOTE: Using screws longer
than 3/16” will damage the
unit and void the warranty.
1U Universal Rack Shelf
Front false
faceplate
uses 2
screws.
1/2 Rack Width Front False
Faceplate
Rack mounting of the amplifier
4. Attach the false front panel (provided with rack shelf part
#60-190-01) to the unoccupied side of the rack (as shown
above), or install a second half-rack-width device in that
side by repeating steps 1 through 3.
5. Attach the rack shelf to the rack using four 10-32 x ¾" bolts
(provided). Insert the bolts through #10 beveled washers,
then through the holes in the rack, as shown above.
Rack mounting ventilation recommendations
Excessive heat can decrease the optimal lifetime of the power
amplifier. An over temp indicator LED on the front panel of
the amplifier lights red whenever the recommended operating
temperature has been exceeded (see "Front Panel Features and
Operation" in chapter 3).
To reduce the chances for an over temp condition, the XPA(s)
should be arranged in a rack environment so that adequate
airow is available both above and below the XPA whenever
possible. No more than two XPAs should be arranged one-
on-top-of-the-other in a rack without an open space between
them, as shown in the following illustration. An XPA can also
be arranged above or below another non-XPA device, but there
must be an open space both above and below those devices.