Programming and Control
PRELIMINARY
View Clip (Max) status 3S 3S
X5
Clipping level:
0 = off (Audio input is set up properly.)
1 = on. (The level or gain is too high, audio
clips/distorts. Output equipment could be
damaged. Adjust the switcher’s input level
so only the Mid/Normal LED is blinking.
The Max/Clip LED should not turn on.)
Additional status commands
View lamp hours status 6S 6S
X205
or
X205
*
X205
X205
represents the number of elapsed hours
of projector lamp use.
The switcher responds with one number unless it has been set up to monitor and report two sets of lamp hours.
Set lamp hours status for 1 lamp
24
X205
*6S
X205
%2A 6S Lhr *
X205
X205
represents the five-digit numeric value
for elapsed lamp use hours, and it is used by
script as a starting point to determine the
number sent in response to the “view lamp
hours” command (6S, above).
Set lamp hours status for 2 lamps
24
X205
*
X205
*6S
X205
%2A
X205
%2A 6S Lhr *
X205
*
X205
View max. lamp hour status 10S 10S
X205
X205
represents the maximum number of
hours of projector lamp use to allow before
changing the lamp. The switcher can be
configured to send an email alert when the
lamp has been used for this number of hours.
Set maximum lamp hours
X205
*10S
X205
%2A 10S LhrMax*
X205
Set maximum allowed projector lamp hours.
View connection status 7S 7S
X216
This command lets you know whether or
not the switcher’s scripts have determined
(based on power polling) if the display is
still connected to the switcher.
X216
=
0 = projector not connected.
1 = projector is connected.
2 = undetermined status.
Set connection status
24
X216
*7S
X216
%2A 7S Pcs
X216
This command is used to reset the projector
connection status flag (
X216
) used by scripts.
Command/response table for SIS commands (continued)
Command ASCII (Telnet) URL Encoded (Web) Response Additional description
(host to switcher) (host to switcher) (switcher to host)