User Guide Manual
SMX System MultiMatrix Switcher • SIS Configuration and Control 35
Establishing an Ethernet Connection
Establish a network connection to the SMX as follows:
1.  Open a TCP socket to port 23 using the SMX IP address.
NOTE:  If the local system administrators have not changed the value, the 
factory-specificed default, 192.168.254.254, is the correct value for this field.
The SMX responds with a copyright message including the date, the name of the 
product, firmware version, part number, and the current date/time (see 
Switcher-Initiated Messages on page 36).
NOTES: 
•  If the SMX is not password-protected, the device is ready to accept SIS 
commands immediately after it sends the copyright message.
•  If the SMX is password-protected, a Password prompt appears below the 
copyright message.
2.  If the SMX is password-protected, enter the appropriate administrator or user 
password.
3.  If the password is accepted, the SMX responds with Login User or Login 
Administrator
.
4.  If the password is not accepted, the Password prompt reappears.
Connection Timeouts
The Ethernet link times out after a designated period of no communication. By default, this 
timeout value is set at 5 minutes but the value can be changed (see the Configure global 
IP port timeout command on page 58).
NOTE:  Extron recommends leaving the default timeout at five minutes and periodically 
issuing the Query (Q) command to keep the connection active. If there are long idle 
periods, Extron recommends disconnecting the socket and reopening the connection 
when another command must be sent.
Number of Connections
An SMX can have up to 200 simultaneous TCP connections, including all http sockets 
and Telnet connections. When the connection limit is reached, the SMX accepts no new 
connections until some have been closed. No error message or indication is given that 
the connection limit has been reached. To maximize performance of an IP Link device, the 
number of connections should stay low and unnecessary open sockets should be closed.
Using Verbose Mode
Telnet connections to the SMX can be used to monitor changes that occur on the switcher, 
such as front panel operations and SIS commands from other Telnet sockets or a serial 
port. For a Telnet session to receive change notices from the SMX, the Telnet session must 
be in verbose mode 1 or 3 (see the Set verbose mode command on page 57).










