Manual
2. — Pull the Cables (at the input locations)
The following cables need to be installed:
• CAT 5 cables for signal transmission from the 
AV wall plates to the PVS 305SA IP
NOTES:
• For PVT RGB D IP Plus four CAT 5 
cables (two for video input and two 
for LAN) are needed, and for PVT RGB 
D wall plates, two CAT 5 signal cables 
for each input are needed.
• Maximum distance from the 
PVS 305SA to the Wallplate is 100 feet. 
The optimum distance is between 
50 and 75 feet. Minimum distance is 
15 feet.
• CAT 5 cables supplied are terminated 
to the TIA 568A standard. Other CAT 5 
cables can be used if they are TIA 568A 
or 568B standards and terminated to 
the same standard at both ends.
• CAT 5 cables (included) for MLC network 
connection.
• PoleVault switcher communication cable from 
the MediaLink controller (MLC PW/RS-232/VC, 
50 feet, part number 26-626-50)
• Projector communication cables from the 
MediaLink controller (IR Serial Comm, 50 feet, 
part number 26-621-50)
a.  Drill cable pathways through any obstructions 
(for example, wall caps, fire-breaks, or 
horizontal studs).
b.  Label the CAT 5 signal cables at both ends with 
the supplied labels. 
c.  Pull the cabling through the wall from the ceiling 
space down to the location of the transmitters 
and other wall devices, and out through the 
openings. 
TIP: Secure cables with cable clamps to 
provide strain relief.
RGB #1A
NOTE: 
Fasten the colored section to the cable 
first, then wrap the clear section around it.
É
 Use the supplied labels for clear cable 
 identication during installation.
Signal Cable Label color
RGB 1A (Input 1 RGB) Orange
RGB 1 B (Input 1 RGB) Orange 
RGB 2A (Input 2 RGB) Yellow
RGB 2B (Input 2 RGB) Yellow
RGB 3A (Input 3 RGB) Magenta
RGB 3B (Input 3 RGB) Magenta
RGB 4A (Input 4 RGB) Light Green
RGB 4B (Input 4 RGB) Light Green
Video 3 (Input 3 Composite Vid) Dark Green
Video 4 (Input 4 Composite Vid) Red
î
 Pull the cables at each location.
PoleVault IP Systems • Installation — Stage 2 (Wallplates and MLC)24










