Manual
2. Pull the Cables (at the input locations)
The following cables need to be installed:
•  STP cables for signal transmission from the 
AV wallplates to the PVS 405D
NOTES:
•  Maximum distance from the 
PVS 405D to the Wallplate is 150 feet. 
•  STP cables supplied are terminated to 
the TIA 568B standard. 
•  PoleVault switcher communication cable 
from the MediaLink controller (MLC PW/ 
RS-232/VC, 50 feet, part number 
26-626-50)
•  Projector communication cables from the 
MediaLink controller (IR Serial Comm, 
50 feet, part number 26-621-50)
a.  Drill cable pathways through any obstructions 
(for example, wall caps, fire-breaks, or 
horizontal studs).
b.  Label the signal cables at both ends with the 
supplied labels. 
c.  Pull the cabling through the wall from the ceiling 
space down to the location of the transmitters 
and other wall devices, and out through the 
openings. 
TIP: Secure cables with cable clamps to 
provide strain relief.
INPUT 1/2
NOTE: 
Fasten the WHITE section to the cable 
first, then wrap the clear section around it.
É
 Use the supplied labels for clear cable 
 identification during installation.
î
 Pull the cables at each location.
PoleVault Digital Systems • Installation — Stage 2 (Wallplates and MLC)30










