Installation User guide
SIS
™
 Programming and Control, cont’d
MLC 226 IP Series • SIS Programming and Control
5-10
PRELIMINARY
Command/response table for SIS commands (continued)
Command ASCII (Telnet)
(host to switcher)
URL Encoded (Web)
(host to switcher)
Response
(switcher to host)
Additional description
Pulse relay
X!
*3*
X6# 
O
X!
%2A3%2A
X6# 
O Rly 
X!
 * 
X%]
Rly 
X!
 * 
X%]
Set a specifi c (
X!
) relay’s pulse time (
X6#
) in 
20 ms increments from 1 (20 ms, minimum) 
to 65535 (1310700 ms, maximum). 
Default pulse length is 25 = 500 ms.
N
  If the verbose mode is enabled, there are two responses from the unit because the relay is pulsed. During a pulse, the relay is toggled to its opposite state and then back to the 
original state.
View the relay state
X! 
O
X! 
O
X%]
  Front panel security lockout modes (executive modes)
Disable lockout modes
24
0X 0X
Exe 0
]
Default setting. Adjustments and selections 
can be made from the front panel in 
addition to via RS-232, Telnet, or Web 
browser.
24
 = The MLC responds with an E24 error 
(privilege violation) if the connected user is 
not logged in at administrator security level.
Enable lockout mode 3
24
3X 3X
Exe 3
]
Lock all front panel selections and 
adjustments via MLC, control modules, SCP, 
and IR remote. Make selections, changes, 
and confi gure features via RS-232 or Web/
Ethernet only. All front panels in the control 
system are locked.
View the lockout mode status X X
X20(]
Show lockout (executive mode) status.
X20(
 = 0 (off, unlocked) or 3 (front panels, 
control modules, and remote control 
locked/disabled).
Example:
XX
0
]
Executive mode is off.
Status commands
View lamp hours status 6S 6S
X20%]
 or 
X20%
*
X20%] X20%
 represents the number of elapsed 
hours of projector lamp use. The MLC 
responds with two sets of lamp hours only 
if two lamp hours have been set. If a lamp’s 
status has not been set, it is shown as the 
default (99999 hours) or “N/A”.