MCP 1000 • Installation
Installation, cont’d
2-6
MCP 1000 • Installation
2-7
Cables must be made with the appropriate connector on each 
end. Regardless of the connector that is being used, the wiring 
must be one-to-one (for example, red-to-red and A-to-A).
CAUTION
  Damage may occur to circuits if cable wire 
assignments are not the same on both ends.
  The total cable length for connecting MCP 1000s and 
MKP 1000s to a matrix system must not exceed 1000 feet 
(305 meters).
To attach connectors to the cables,
1.  Trim approximately 1.5 inches of the cable jacket to expose 
the four insulated wires and a bare drain (ground) wire 
(silver colored).
Trimming the cable jacket
2.  Cut off and discard the foil shield.
3.  Strip 0.25 inches of insulation from each of the four wires.
4.  Twist the strands of the black 
wire, insert it into the opening 
that corresponds to pin E, and 
tighten its captive screw. (See the 
illustration at right.)
5.  Twist the strand of the drain 
wire, insert it into position D, and 
tighten its captive screw.
6.  Connect the remaining wires in 
the same way (for this example, 
white, violet, and red).
ED
COMM-LINK PORT
CBA EDCBA
5 mm captive
screw connector
Wiring the 5 mm captive screw plugs
7.  Choose the appropriate captive screw connector and repeat 
steps 1 through 6 for each cable end.
Both types of captive screw connectors use a “moving cage” to 
damp the wires, without the need for soldering.
Extron’s Plenum Comm-Link cable
Extron’s Plenum Comm-Link cable was designed for use with 
the MCP 1000 and MKP 1000. If another cable will be used, it 
must meet the following specifi cations:
A (red) — 18 AWG
B (violet or blue) — 22 AWG (grouped and shielded)
C (white) — 22 AWG
D (drain) — 24 AWG
E (black) — 18 AWG
See appendix A, "Specifi cations, Part Numbers, and 
Accessories," for a list of Extron cable part numbers.
1
3.5 mm captive
screw connector on
MCP 1000