8. Apply heat to shrink the tubing over the power lug and wire insulation.
The installed tubing on the power lug should appear similar to the example in the following gure.
FIGURE 28 Heat shrink tubing and power lug on DC power supply cable
1. Heat shrink tubing 2. Power lug
9. Connect the power lugs to the power supply module.
Connect the -48V wire to the negative terminal and the 0V wire to the positive terminal.
NOTE
The DC return must be isolated from the chassis ground (DC-I) when making connections to the power supply.
FIGURE 29 DC power supply
1. DC power lug 1 2. DC power lug 2
Providing power to the device