FIGURE 59 Switch fabric module - SLX 9850-4
1. Power LED: Green - Power OK; O - No power 2. Status LED: Green - Status OK; Amber - Alert; O - Unexpected error
Precautions specic to the switch fabric module
Before you remove a switch fabric module, you must
rst remove the fan module. For more information, refer to Removing a fan module
on page 116.
NOTE
The fan module must be reinstalled within 20 minutes to prevent overheating.
NOTE
The ambient intake temperature of the system must be less than 35 deg C (95 deg F) at sea level to prevent overheating. If the
ambient temperature is greater than 35 deg C, the module installation time must be reduced. Refer to the specic module
removal and installation instructions in this guide for more details.
In addition, wear a wrist grounding strap connected to chassis ground (if the device is plugged in) or a bench ground. Refer to ESD
ground strap connection points on page 88 for the location of the ESD jack.