Installation Guide
Table Of Contents
- ExtremeRouting SLX 9850-8 Hardware Installation Guide
- Preface
- About this Document
- Device Overview
- Preparing for the Installation
- Mounting the Device
- Initial Setup and Verification
- Initial setup and configuration checklist
- Items required
- Providing power to the device
- Establishing a serial connection
- Configuring a static IP address
- Establishing an Ethernet connection
- Customizing the chassis and host names
- Configuring the DNS service
- Setting the date and time
- Verifying correct operation
- Backing up the configuration
- Powering down the device
- Installing cable management kit
- Monitoring the Device
- Management Modules
- Interface Modules
- Power Supply Modules
- Power supply module overview
- Precautions specific to the power supply module
- Time and items required for removal and replacement
- Removing an AC power supply module
- Inserting an AC power supply module
- Removing a DC power supply module
- Inserting a DC power supply module
- Verifying power supply module operation
- High Voltage Power Supply Unit supporting AC and DC Voltages
- Fan Modules
- Switch Fabric Modules
- Transceivers and cables
- Supported transceivers and cables
- Time and items required
- Precautions specific to transceivers and cables
- Cleaning the fiber-optic connectors
- Managing cables
- Installing an SFP+ transceiver
- Replacing an SFP+ transceiver
- Installing a QSFP28 transceiver
- Replacing a QSFP28 transceiver
- Breakout cables
- Verifying transceiver operation
- Hardware Maintenance Schedule
- ExtremeRouting SLX 9850 Technical Specifications
- System specifications
- Ethernet
- LEDs
- Other
- Weight and physical dimensions
- Environmental requirements
- Power supply specifications (per PSU)
- Power consumption (typical configuration)
- Power consumption (maximum configuration)
- Power consumption (modules) (typical configuration)
- Power consumption (modules) (maximum configuration)
- Data port specifications (Ethernet)
- Serial port specifications (pinout RJ-45)
- Serial port specifications (protocol)
- Memory specifications
- Regulatory compliance (EMC)
- Regulatory compliance (safety)
- Regulatory compliance (environmental)
- Regulatory Statements
- Cautions and Danger Notices
Power supply specications (per PSU)
Power supply model Maximum
output power
rating (DC)
Input voltage Input line
frequency
Maximum input
current
Input line
protection
Maximum inrush
current
BR-SLX9850-
ACPWR-3000
1390W@100-
120V
2915W@200-
240V
1390W Output:
100-120V
(nominal)
90–132 V (range)
2915W Output:
200 - 240 VAC
(nominal)
180–264 V (range)
50/60 Hz 16 A Line & Neutral
Fused
60 A peak for <10
ms, 10 ms - 150
ms <25 A peak,
>150 ms <16 A
BR-SLX9850-
DCPWR-3000
3000 W —48 VDC (nominal)
—40-60 VDC
(range)
N/A 90 A Input fuse on —48
VDC input
<70 A peak initial
current surge or
spike of <10 ms
High Voltage AC
(HVAC)
3000 W HV AC,
100V-120VAC.
200V-277VAC
High Voltage DC
(HVDC)
3000 W HV DC,
240V-380V DC
Power consumption (typical conguration)
Conguration
of SLX 9850-4: One 4-slot chassis with one management module, ve switch fabric modules, two power supplies, three
fan modules, and four 36-port 100GbE, 60-port 40GbE, or 240-port 10GbE ex-speed interface modules set in 60x40 mode.
Interface cards are enabled and optics/Trac are at 50% line rate. Random packets, fans at nominal speed, ambient temperature 25 deg
C.
Conguration of SLX 9850-8: One 8-slot chassis with one management module, ve switch fabric modules, four power supplies, three
fan modules, and eight 36-port 100GbE, 60-port 40GbE, or 240-port 10GbE ex-speed interface modules set in 60x40 mode.
Interface cards are enabled and optics/Trac are at 50% line rate. Random packets, fans at nominal speed, ambient temperature 25 deg
C.
Model name Power used in watts Minimum number of power
supplies
Notes
SLX 9850-4 3958 2 200 VAC amps, watts, and BTU/hr
are calculated with 0.98 power
factor and 2 PSUs
SLX 9850-8 7773 4 200 VAC amps, watts, and BTU/hr
are calculated with 0.98 power
factor and 4 PSUs
Power consumption (maximum conguration)
Conguration of SLX 9850-4: One 4-slot chassis with two management modules, six switch fabric modules, six power supplies, three
fan modules, and eight 36-port 100GbE, 60-port 40GbE, or 240-port 10GbE ex-speed interface modules set in 60x40 mode.
Power consumption (maximum conguration)
ExtremeRouting SLX 9850-8 Hardware Installation Guide