Managing the cooling system
* The fan-threshold values in brackets are for 8-slot devices.
For information about checking the current low and high temperature threshold settings for modules and fan speeds, refer to “Displaying
temperature thresholds for modules and fan speeds” on page 225.
NOTE
Adjusting fan controls out of the default setting can negatively affect the efficient cooling of blades and may cause a blade to
overheat and shutdown.
You can change the default low and high temperature thresholds for a particular module and fan speed. For example, to change the low
and high thresholds of the medium fan speed for the management modules to 56 C and 72 s C, respectively, enter the following
command at the global CONFIG level of the CLI.
Brocade(config)# fan-threshold mp med 56 72
Syntax: fan-threshold <module> [low <high-threshold>] [med <low-threshold> <high-threshold>] [med-hi <low-threshold>
<high-threshold>] [high <low-threshold> <high-threshold>]
For the module parameter, you can specify the following:
• lp – Changes low and high temperature thresholds for Gen 1 interface modules
• lp2 – Changes low and high temperature thresholds for Gen 2 interface modules
• mp – Changes low and high temperature thresholds for management modules
Generation 2 Interface modules
High 56 C95 C
Medium-high 51 C60C
Medium 46C55C
Low –1 50 C
Generation 2 Interface modules Packet Processor
High 70 C113 C
Medium-high 60 C80C
Medium 45C65C
Low –1 50 C
Switch fabric module
High 47 C75 C
Medium-high 37 C50C
Medium 27C40C
Low –1 30 C
High-Speed Switch fabric module
High 65 C100 C
Medium-high 55 C70C
Medium 45C60C
Low –1 50 C
TABLE 37 Default temperature thresholds for modules and fan speeds for Brocade MLX and NetIron XMR devices (Continued)
Fan speed Low temperature threshold High temperature threshold