Installation Guide
Brocade MLX Series and Brocade NetIron XMR Installation Guide 183
53-1004195-02
Installing a NetIron XMR 32000 router
DRAFT: BROCADE CONFIDENTIAL
For the NEBS-compliant installation of a NetIron XMR 4000, 8000, and 16000 routers with AC and DC
systems, use a ground wire of at least 6 American Wire Gauge (AWG). The ground wire should have an
agency-approved crimped connector (provided with the router) attached to one end, with the other end
attached to building ground. The connector must be crimped with the proper tool, allowing it to be
connected to both ground screws on the enclosure. Before crimping the ground wire into the provided
ground lug, insure the bare copper wire has been cleaned and antioxidant is applied to the bare wire.
To ensure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is required to
be applied to the mounting hardware used to attach the ground lug.
FIGURE 134 Crimping the power supply wire in the lug
4. Reconnect the power lugs to the power supply unit.
5. Replace the safety cover. Refer to Figure 135.
FIGURE 135 Attaching the safety cover
6. Connect the wire to your DC power source, making sure to connect the -48V cable to the negative terminal on the power supply
and the 0V cable to the positive terminal as marked on the power supply.
1 #4 AWG power supply wire 2 Power lug
2
1
1
2