53-1004195-02
Installing a NetIron XMR 8000 router
DRAFT: BROCADE CONFIDENTIAL
FIGURE 107 The NetIron XMR 8000 DC power supply
3. Use a #2 Phillips screwdriver to remove the power lugs, as shown in Figure 107.
4. Crimp the correct AWG power supply wire into the power lugs and reconnect the lugs to the power supply:
For a 1200 W power supply, crimp #8 AWG
For a 1800 W power supply, crimp #6 AWG
For the NEBS-compliant installation of a NetIron XMR 4000, 8000, and 16000 routers with AC and DC
system use a ground wire of at least 6 American Wire Gauge (AWG). The ground wire should have an
agency-approved crimped connector (provided with the router) attached to one end, with the other end
attached to building ground. The connector must be crimped with the proper tool, allowing it to be
connected to both ground screws on the enclosure. Before crimping the ground wire into the provided
ground lug, insure the bare copper wire has been cleaned and antioxidant is applied to the bare wire.
To ensure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is required to
be applied to the mounting hardware used to attach the ground lug.
FIGURE 108 Crimping the power supply wire in the lug
1 Screws holding transparent cover 2 Screws holding power lugs