Installing a NetIron XMR 8000 router
For the NEBS-compliant installation of a NetIron XMR 4000, 8000, and 16000 routers with AC and DC
systems, use a ground wire of at least 6 American Wire Gauge (AWG). The ground wire should have an
agency-approved crimped connector (provided with the device) attached to one end, with the other end
attached to building ground. The connector must be crimped with the proper tool, allowing it to be
connected to both ground screws on the enclosure. Before crimping the ground wire into the provided
ground lug, insure the bare copper wire has been cleaned and antioxidant is applied to the bare wire.
To ensure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is required to
be applied to the mounting hardware used to attach the ground lug.
FIGURE 100 Crimping the power supply wire in the lug
4. Connect the -48V cable to the negative terminal on the power supply and the 0V cable to the positive terminal on your DC
power source.
NOTE
DC return must be isolated from the device ground (DC-I) when connecting to the power supply.
5. Replace the transparent cover.
This equipment installation must meet NEC/CEC code requirements. Consult local authorities for regulations.