Managing the cooling system
* The fan-threshold values in brackets are for 8-slot devices.
For information about checking the current low and high temperature threshold settings for modules and fan speeds, refer to “Displaying
temperature thresholds for modules and fan speeds” on page 227.
NOTE
Adjusting fan controls out of the default setting can negatively affect the efficient cooling of blades and may cause a blade to
overheat and shutdown.
You can change the default low and high temperature thresholds for a particular module and fan speed. For example, to change the low
and high thresholds of the medium fan speed for the management modules to 56° C and 72 °s C, respectively, enter the following
command at the global CONFIG level of the CLI.
Brocade(config)# fan-threshold mp med 56 72
Syntax: fan-threshold <module> [low <high-threshold>] [med <low-threshold> <high-threshold>] [med-hi <low-threshold>
<high-threshold>] [high <low-threshold> <high-threshold>]
For the module parameter, you can specify the following:
lp – Changes low and high temperature thresholds for Gen 1 interface modules
lp2 – Changes low and high temperature thresholds for Gen 2 interface modules
mp – Changes low and high temperature thresholds for management modules
Generation 2 Interface modules
High 56° C95° C
Medium-high 51° C60° C
Medium 46° C55° C
Low –1° 50° C
Generation 2 Interface modules Packet Processor
High 70° C 113° C
Medium-high 60° C80° C
Medium 45° C65° C
Low –1° 50° C
Switch fabric module
High 47° C75° C
Medium-high 37° C50° C
Medium 27° C40° C
Low –1° 30° C
High-Speed Switch fabric module
High 65° C 100° C
Medium-high 55° C70° C
Medium 45° C60° C
Low –1° 50° C
TABLE 38 Default temperature thresholds for modules and fan speeds for Brocade MLX and NetIron XMR devices (Continued)
Fan speed Low temperature threshold High temperature threshold