Technical Specs

Power supply
model
Maximum output
power rating (DC)
Input voltage Input line
frequency
Maximum input
current
Input line
protection
Maximum inrush
current
<25 A peak for
cycles 10 ms -
150 ms
N/A 1200 W -48 VDC(nominal)
-40 to -60 VDC
(range)
N/A 40 A -Ve Fused <80 A peak for
<10 ms at cold or
warm start
BR-MLXE-
DCPWR-1800
1800 W -48 VDC (nominal)
-40 to -60 VDC
(range)
N/A 60 A -Ve Fused <80 A peak for
<10 ms at cold or
warm start
MLXe-32 router
N/A 2400 W 200-240 VAC
(nominal)
180-264 VAC
(range)
50/60 Hz
(nominal)
47 - 63 Hz (range)
16 A Line Fused <60 A peak for
<10 ms at cold or
warm start
<25 A peak for
cycles 10 ms -
150 ms
N/A 2400 W -48 VDC (nominal)
-40 to -60 VDC
(range)
N/A 75 A -Ve Fused <70 A peak for
<10 ms at cold or
warm start
BR-MLXE-32-
DCPWR-3000
3000 W -48 VDC (nominal)
-40 to -60 VDC
(range)
N/A 80 A -Ve Fused <70 A peak for
<10 ms at cold or
warm start
Power consumption (maximum conguration)
NOTE
The MLX-32 device does not support 100 VAC input power.
Model name @100 VAC input @200 VAC input @-48 VDC input Minimum number of
power supplies
Notes
Maximum per MLX (using 8x10G-D, 8x10G-M, 4x10G, 2x10G, 1G modules only)
MLXe-4 17 A
1730 W
5905 BTU/hr
9 A
1730 W
5905 BTU/hr
36 A
1730 W
5905 BTU/hr
1200W - 2
1800W - 1
MLXe-8 33 A
3332 W
11372 BTU/hr
17 A
3332 W
11372 BTU/hr
70 A
3332 W
11372 BTU/hr
1200W - 3
1800W - 2
MLXe-16 57 A
5674 W
19365 BTU/hr
28 A
5674 W
19365 BTU/hr
118 A
5674 W
19365 BTU/hr
1200W - 4
1800W - 3
MLXe-32 N/A 57 A
11414 W
38958 BTU/hr
238 A
11414 W
38958 BTU/hr
2400W - 4
3000W - 4
Power consumption (maximum conguration)
ExtremeRouting MLX Series Technical Specications