The following table lists power consumption information for MLX Series routers with all base components installed, and with only the
specied interface modules installed.
TABLE 49 MLX Series router power consumption values
Model @100 VAC @200 VAC @-48VDC Minimu
m
number
of
1200W
power
supplies
needed
Minimu
m
number
of
1800W
power
supplies
needed
Minimu
m
number
of
2400W
power
supplies
needed
Minimu
m
number
of
3000W
power
supplies
needed
Amps Watts BTU/hr Amps Watts BTU/hr Amps Watts BTU/hr
MAXIM
UM
PER
MLX
(using
8x10G-
D,
8x10G-
M,
4x10G,
2x10G,
1G
module
s only)
MLX-4 17 1730 5905 9 1730 5905 36 1730
5905 2 1
MLX-8 34 3356 11453 17 3356 11453 70 3356 11453 3 2
MLX-1
6
57 5698 19446 28 5698 19446 119 5698 19446 4 3
MLX-3
2
N/A N/A N/A 57 11414 38958 238 11414 38958 4 4
MAXIM
UM
PER
MLX
(any
module)
MLX-4 21 2083 7108 10 2083 7108 43 2083 7108 2 1
MLX-8 41 4060 13858 20 4060 13858 85 4060 13858 3 2
MLX-1
6
71 7107 24255 36 7107 24255 148 7107 24255 5 4
MLX-3
2
N/A N/A N/A 71 14232 48575 297 14232 48575 5 4
Physical dimensions
The following table provides the physical dimensions for MLX Series routers.
Hardware specications for ExtremeRouting MLX Series routers
Extreme Routing MLX Series Hardware Installation Guide