Installation Guide

Table Of Contents
FIGURE 88 Removing the safety cover (2400W power supply and 3000W power supply displayed)
2. Use a #2 Phillips screwdriver to unscrew the power lugs. Refer to the following figure.
FIGURE 89 Removing the power lugs (2400W power supply and 3000W power supply displayed)
1. Power lug screws
2. Power lug
3. Crimp the correct AWG power supply wire into the power lugs. For 2400W power supplies: #4 AWG power supply wire. For
3000W power supplies: #2 AWG power supply wire. Refer to the following figure.
CAUTION
For a Brocade MLXe Series-32 AC system, use a ground wire of at least 2 American Wire Gauge (AWG). The ground
wire should have an agency-approved crimped connector (provided with the chassis) attached to one end, with the
other end attached to building ground. The connector must be crimped with the proper tool, allowing it to be
connected to both ground screws on the enclosure.
Installing a Brocade MLXe Router
Brocade NetIron MLXe Series Hardware Installation Guide
166 53-1004203-03