CAUTION
For a DC system, use a grounding wire of at least 6 American Wire Gauge (AWG). The 6 AWG wire should be
attached to an agency-approved crimp connector crimped with the proper tool. The crimp connector should allow for
securement to both ground screws on the enclosure. For the Ground lug, use UL listed Panduit crimp connector, P/N
LCD6-10A, and two 10-32, PPH, screws to secure crimp connector to chassis. Grounding position is located on the
side of the chassis adjacent ground symbol.
NOTE
To ensure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is required to be applied
to the mounting hardware used to attach the ground lug.
FIGURE 39 Crimping the power supply wire in the lug
1. AWG power supply wire: #8 AWG power supply wire for
1200W power supplies#6 AWG power supply wire for
1800W power supplies
4. Connect the -48V cable to the negative terminal and the 0V cable to the positive terminal.
NOTE
DC return must be isolated from the router ground (DC-I) when connecting to DC power supplies.
5. Replace the transparent cover.
This equipment installation must meet NEC/CEC code requirements. Consult local authorities for regulations.
Final steps
Complete these final steps in the order listed:
1. Perform the step Attaching a management station on page 168.
2. Perform the step Activating the power source on page 168.
3. Perform the step Verifying proper operation on page 169.
Installing a Brocade MLXe Series-16 router
The following sections describe how to install a Brocade MLXe Series-16 router.
NOTE
Illustrations may differ slightly from the actual equipment.
Installing a Brocade MLXe Router
Brocade NetIron MLXe Series Hardware Installation Guide
110 53-1004203-03