Installation guide

2-2 B
LACK
D
IAMOND
H
ARDWARE
I
NSTALLATION
G
UIDE
I
NSTALLATION
AND
S
ETUP
D
ETERMINING
THE
S
YSTEM
L
OCATION
The BlackDiamond is suited for use in a wiring closet or equipment room, where it can
be mounted in a standard 19-inch equipment rack. Mounting brackets are integrated
with the chassis.
When deciding where to install the BlackDiamond, ensure that
The system is accessible and cables can be connected easily.
Water or moisture cannot enter the chassis.
Air-flow around the unit and through the vents at the rear of the chassis is not
restricted. A minimum of 3 inches is required (5 inches recommended) for clearance.
Temperature operating limits of 0° to 40° C are not exceeded.
I
NSTALLING
THE
B
LACK
D
IAMOND
The BlackDiamond can be mounted in a rack. The chassis is 15U high and fits in most
standard 19-inch racks.
The BlackDiamond chassis is shipped empty; you must install the power supply and
module cards after rack-mounting the empty chassis.
Rack-mount the chassis before installing any BlackDiamond components.
To install the BlackDiamond, follow these steps:
1 Mount the helper bracket in the rack using four appropriate rack-mounting screws,
as shown in Figure 2-1.