The Alpine 3800 series switch is suited for use in a wiring closet or equipment room,
where it can be mounted in a standard 19-inch equipment rack. Mounting brackets are
integrated with the chassis.
When deciding where to install the Alpine 3800 series switch, ensure the following:
The switch is accessible and cables can be connected easily.
Water or moisture cannot enter the chassis.
Air-flow around the unit and through the vents at the sides of the chassis is not
restricted. A minimum of 3 inches is required (5 inches recommended) for clearance.
Temperature operating limits of 0° to 40° C are not exceeded.
I
NSTALLING
THE
A
LPINE
3800
SERIES
SWITCH
The Alpine 3800 series switch fits in standard 19-inch racks.
The Alpine 3800 series switch chassis is shipped empty; you must install the power
supply and modules after rack-mounting the empty chassis.
Warning: Rack-mount the chassis before installing any Alpine 3800 series switch
components.
To install the Alpine 3800 series switch in a standard 19-inch rack, follow these steps:
1 Mount the helper bracket in the rack using four appropriate rack-mounting screws,
as shown in Figure 2-1.