CHIMNEY OR INDIVIDUAL FLUE
The chimney or individual ue must respond to the following requisites:
seal the combustion products, be waterproof and adequately insulated in line with the use conditions;
be realised with materials which resist the normal mechanical stress, heat, action of the combustion products and any
condensate;
have mainly vertical progress with deviations from the axis not higher than 45°;
be adequately distanced from fuel or ammable materials through air space or opportune insulation;
have preferably circular internal section: the square or rectangular sections must have round corners with a radius not
lower than 20 mm;
have constant internal section, free and independent;
have rectangular section with max. ratio between the sides of 1.5.
It is recommended that the smoke pipe be equipped with a collection chamber for solid materials and any condensate situated
under the smoke channel inlet, so that it can be easily opened and inspected from airtight door.
REFERENCES INFLAMMABLE OBJECTS NONINFLAMMABLE OBJECTS
A 200 mm 100 mm
B 1,500 mm 750 mm
C 200 mm 100 mm
Minimum 80 cm
2
S= oor protection
Air inlets
Chimney cap
windproof
Flue
Inspection
Inspection
Flue
Inspection