Product Manual

MA260enGB_V1.15/15
2
Introduction
ThankyouforselectingtheExtechMA260200ATrueRMSOpenJawClampMeter.TheMA260
incorporatesAutoSensingwherethemeasurementtypeisautomaticallysensedandconfigured,
noneedtoturnadialtoselectthemeasurementtypeorrange.ForACVoltage,theAutosense
featurealsoevaluatesinput
signalsandadjuststheInputImpedancetoeliminateeffectsofghost
voltages.
TheMA260measuresACcurrent,AC/DCVoltage,Resistance,Continuity,andDiodeandoffers
extralargedisplaydigits,datahold,andadisplaybacklightfunction.Thenon contactVolt
Detectionfeaturesenseselectricalsourcessafely.
Thisdeviceisshippedfullytestedandcalibratedand,withproperuse,willprovideyearsofreliable
service.Pleasevisitourwebsite(www.extech.com)tocheckforthelatestversionofthisUser
Guide,ProductUpdates,ProductRegistration,andCustomerSupport.
SafetyInformation
Toensurethesafeoperationandserviceofthemeter,followtheseinstructionsclosely.Failureto
observewarningscanresultinsevereinjury.
WARNINGS
WARNINGSidentifyhazardousconditionsandactionsthatcouldcauseBODILYHARMorDEATH.
Thetimedelaythatresultsfromthemeter’sautomaticsensingcircuit(1to2seconds)maycauseGFCI
circuitstoresetandbreakerstotrip.
ItisnotrecommendedtousecalibrationequipmenttotesttheMA260.Calibratorscanbedamagedif
usedtotesttheMA260.
IndividualprotectiveequipmentshouldbeusedifHAZARDOUSLIVEpartsintheinstallationwhere
measurementsaretobecarriedoutcouldbeaccessible.
Iftheequipmentisusedinamannernotspecifiedbythemanufacturer,theprotectionprovidedbythe
equipmentmaybeimpaired.
Alwaysuseproperterminals.
Toreducetheriskoffireorelectricshock,donotexposethisproducttorainormoisture.
Verifythemeteroperationbymeasuringaknowncurrent.Ifindoubt,havethemeterserviced.
Donotapplymorethantheratedvoltage/currentasmarkedonthe
meter.
Toavoidfalsereadingsthatcanleadtoelectricshockandinjury,replacebatteryassoonasthelow
batteryindicatorappears.
Donotusethemeterinoraroundexplosivegasorvapor.
Whenusingtestleadsorprobes,pleasekeepfingersbehindthefingerguards.
Removetestleadsfromthemeterbeforeopeningthebatterycompartmentorthemetercase.
Usecautionwithvoltagesabove30VACrms,42VACpeak,or60VDC.Thesevoltagesposeashockhazard.
ProbeassembliestobeusedforMAINSmeasurementsmustberatedasappropriateformeasurement
Category
IIIorIVaccordingtoIEC61010031andmusthaveavoltageratingofatleastthevoltageof
thecircuittobemeasured.
Donotexposemetertoextremesintemperatureorhighhumidity.
Deenergizetheinstallationundertestorwearsuitableprotectiveclothingwhenplacing
orremoving
theflexiblecurrentprobefromatestsetup.
Donotapply/removetheflexiblecurrentprobeto/fromUNINSULATEDHAZARDOUSLIVEconductors
whichmaycauseelectricshock,electricburn,orarcflash.