Enclosure Double molded, Waterproof (IP64)
Diode Test Test current of 0.9mA maximum, open circuit voltage 2.8V DC
typical
Continuity Check Audible signal will sound if the resistance is less than 35Ω
(approx.), test current <0.35mA
PEAK Captures peaks >1ms
Memory Store and recall up to 3 values
Temperature Sensor Requires type K thermocouple
Input Impedance >10M VDC & >3M VAC
AC Response True rms
ACV Bandwidth 40Hz to 1000Hz
IR Spectral response 6 to 16µm
IR Emissivity 0.95 fixed
IR distance ratio 30:1
Laser pointer Class 2 laser < 1mW power; Wavelength is 630 to 670nm
Crest Factor 3 at full scale up to 500V, decreasing linearly to 1.5 at 1000V
Display 40,000 count backlit liquid crystal display with bargraph
Overrange indicationOL” is displayed
Auto Power Off 15 minutes (approximately) with disable feature
Polarity Automatic (no indication for positive); Minus (-) sign for negative
Measurement Rate 2 times per second, nominal
Low Battery Indication
+
is displayed if battery voltage drops below operating
voltage
Battery One 9 volt (NEDA 1604) battery
Fuses mA, µA ranges; 0.5A/1000V ceramic fast blow
A range; 10A/1000V ceramic fast blow
Operating Temperature 41ºF to 104ºF (5ºC to 40ºC)
Storage Temperature -4
o
F to 140
o
F (-20
o
C to 60
o
C)
Operating Humidity Max 80% up to 87ºF (31ºC) decreasing linearly to 50% at 104ºF
(40ºC)
Storage Humidity <80%
Operating Altitude 7000 ft. (2000 meters) maximum
Weight 0.753 lb (342 g) (includes holster)
Size 7.36” x 3.2” x 2.0” (187 x 81 x 50 mm) (includes holster)
Safety This meter is intended for origin of installation use and protected,
against the users, by double insulation per EN61010-1 and
IEC61010-1 2
nd
Edition (2001) to Category IV 600V and Category
III 1000V; Pollution Degree 2.
Approvals CE