Product Manual

382357 V2.2 09/10 9
Applications
Telephone-Electrical Ground Rods
1. Remove any protective covering from the ground conductor
2. Turn the meter switch to the Ohm
function.
3. Once the start-up calibration procedure is completed clamp on to an electrode or
ground rod.
4. Allow several seconds for the meter to settle and then note the reading.
Cellular Transmission Towers
WARNING: Use extreme care when making measurements around transmission towers;
High Voltage may be present.
The ground conductor should be located at the base of the tower, but your configuration
may be different.
1. Locate the ground conductor
2. Clamp around the ground conductor. You should place the clamp before any splices,
bonds or other splits in the ground system.
3. Read the measured reading.
Transmission
Tower
Primary
Ground Conductor
Branch
Ground Conductors
Cement Pad