Measurement Specifications
Measurement
Range Resolution Accuracy
Earth Ground
Resistance
20Ω 0.01Ω
± (2% reading + 10 digits)
200Ω 0.1Ω
± (2% reading + 3 digits)
2000Ω 1Ω
Earth Voltage
Frequency: 40 to
500Hz
0 to 200VAC
0.1V ± (3% reading +3digits)
Resistance
0 to 200kΩ
0.1kΩ
± (1% reading +2 digits)
Overload Protection: 250 Vrms
AC Voltage
40 Hz to 400Hz
0 to 750V 1V ± (1.2% reading +10 digits)
Overload Protection: 750 Vrms, Input Impedance: 10MΩ
DC Voltage
0 to 1000V 1V ± (0.8% reading +3 digits)