User Manual
MA61_MA63-en-GB_V1.0 3/15
15
Specifications
GeneralSpecifications
Display 6000countLCDwithmultifunctionindicators
Fullscale6200countsforCapacitancefunction
Fullscale9999countsforFrequencyfunction
LEDlamp ForNon‐ContactVoltageDetector
Functions Current(ACA,DCA),Voltage(VAC,VDC),Resistance,
Capacitance,Frequency,Non‐ContactVoltagedetector,
Continuity,andDiodetest
Polarity “‐“indicatesnegativepolarity(positivepolarityassumed)
Currentsensor Halleffect
Overloadindication O.L
DCAzeroadjust MA63:One‐touchZERObutton(alsousedasaRelative
function);MA61:RELbutton(Relative)
Displayrate 2~3readings/second
Battery Two1.5VAAAbatteries
Operatingtemperature 0
0
Cto40
0
C(32
0
Fto104
0
F)
OperatingHumidity <75%RH0~30C(32
0
Fto86
0
F)
<50%RH30~40C(86
0
Fto104
0
F)
Storagetemperature‐10
0
Cto50
0
C(14
0
Fto122
0
F)
Altitude 2000m(6562’)
Powerconsumption 20mADCapprox.
Weight 170g(6.0oz.)includingbattery
Dimensions 175x60x33.5mm(6.9x2.4x1.3”)(HxWxD)
Jawopening 17mm(0.7”)3000MCM
Standards IEC/EN61010‐1,EN61010‐2‐033,EN61010‐2‐032;CategoryIII
300V,CategoryII600V;pollutionclass2
Electromagnetic
compatibility
<1V/mRFfield:Overallaccuracy= specifiedaccuracy+5%of
therange.Unspecifiedindicationfor1V/mRFfield.
TestLeads UseonlytestprobesratedCATII600V,CATIII300Vorbetter
thatmeettherequirementsofIEC61010‐031