APPENDIX C – SINGLE PHASE TECHNICAL DATA
S
INGLE PHASE
M
AXIMUM AC AMPS (RMS)
S
HIPPING DATA
FLX or SCR Amp DC DC 120 208 240 480 600 Cabinet WEIGHT
Model Numbers Hour Volts Amps VAC VAC VAC VAC VAC Size Lbs KG
200-06-260S1 260 12 40 11.6 6.7 5.8 2.9 M4 79 36
200-06-475S1 475 12 75 21.0 12.5 10.8 5.4 4.3
2.3
M4 97 44
200-06-600S1 600 12 95 28.0 16.2 14.0 7.0 5.6 M4 101 46
200-06-865S1 865 12 135 22.6 19.6 9.8 7.8 M4 125 57
200-06-965S1 965 12 150 25.2 21.8 10.9 8.7 M4 154 70
200-09-475S1 475 18 75 16.9 14.6 7.3 5.8 M4 114 52
200-09-600S1 600 18 95 21.5 18.6 9.3 7.4 M4 119 54
200-09-865S1 865 18 135 30.5 26.4 13.2 10.6 M4 143 65
200-09-965S1 965 18 150 33.9 29.4 14.7 11.8 M4 178 80
200-12-260S1 260 24 40 19.7 11.3 9.8 4.9 4.0 M4 95 43
200-12-475S1 475 24 75 21.2 18.4 9.2 7.4 M4 134 61
200-12-600S1 600 24 95 27.0 23.4 11.7 9.4 M4 145 66
200-12-750S1 750 24 115 32.6 28.2 14.1 11.3 M4 163 74
200-12-865S1 865 24 135 38.3 33.2 16.6 13.3 M4 169 77
200-12-965S1 965 24 150 42.5 36.8 18.4 14.7 M4 198 90
200-18-260S1 260 36 40 16.0 13.8 6.9 5.5 M4 136 62
200-18-475S1 475 36 75 30.0 26.0 13.0 10.4 M4 158 72
200-18-600S1 600 36 95 37.9 32.9 16.4 13.1 M4 163 74
200-18-750S1 750 36 115 45.9 39.8 19.9 15.9 M5 216 98
200-18-865S1 865 36 135 46.6 23.3 18.7 M5 238 108
200-24-260S1 260 48 40 20.6 17.8 8.9 7.2 M5 132 60
200-24-475S1 475 48 75 38.6 33.4 16.7 13.4 M5 198 90
200-24-600S1 600 48 95 48.9 42.4 21.2 16.9 M5 242 110
*DC FUSE MUST BE A FAST ACTING FUSE CAPABLE OF PROTECTING SEMICONDUCTORS.
Charger Output Current (Amps) DC Fuse Rating (Amps) (LET/LMT)
40
75
95
115
135
150
165
185
225
265
63
100
125
180
180
200
200
250
250
355
Sales • Service • Recycling 888.563.6300 in the USA 800.268.2698 in Canada