APPENDIX A – FAULT CODES
CODE STATUS DESCRIPTION
F01 N Over discharged battery (<1.90vpc after 30 seconds of charge)
F02 N Deep discharged battery (<1.90vpc after 30 seconds of charge > 1.90vpc)
F03 N Sulphated battery
F04 S Charger over heating
F05 S Mains failed during charge
F06 R No output current
F07 C Incorrect battery < 1.70
F07 (+Y led on) C Incorrect battery > 2.25
F09 C Bulk charge time-out
F10 C Second stage time-out (Profile Dependant)
F11 C Incorrect Mains Frequency
F12 C Control hardware (MCU)
F13 S Thermistor fault
F16 S Battery overheating (if temp probe fitted)
F17 C Auto balance charge time-out
F18 C Battery disconnected without pausing charge
F19 C Battery disconnected in cool down period
Key: -
C = critical fault Ö charge stopped Ö fault code displayed permanently
S = suspend fault Ö charge suspended until criteria fulfilled Ö fault code displayed permanently
R = retry fault Ö charge retries after 20 seconds Ö fault code display alternating with standard
display
N = non-critical fault Ö charge continues Ö fault code display alternating with standard display