User Manual

APPENDIX G
92
UL DATA
CAUTION
To operate this charger from inputs other than 120 Vac, you must
use branch circuit protection. To reduce the risk of fire, use only
on circuits provided with the following branch circuit protection
in accordance with the National Electrical Code, ANSI/NFPA 70.
Charger Voltage Rating Current
Rating
48 Vdc 130 Vdc 48 Vdc 130 Vdc
12 Adc
--- 25A --- 20A
16 Adc
15A 25A 12A 20A
20 Adc
20A 30A 15A 30A
25 Adc
25A 40A 20A 35A
208 Vac Branch Circuit
Protection (Amperes)
240 Vac Branch Circuit
Protection (Amperes)
NOTE: This table does not apply to AT10.1 chargers with 480 Vac input.